What are the different modes of DFWCS?
When do they take affect?
What is main difference?
Low power mode & Hi power mode
Up power - @ 25% switches to Hi power mode
Down power- @ 15% switches to Lo power mode
Hi power compares Lvl setpoint vs. lvl act & stm flow vs. feed flow
Lo power doesn’t use stm & feed flows due to inaccuracies @ low power, instead uses WR S/G lvl
What is arbitration? What signals use arbitration in DFWCS?
A method of signal validation for parameters that
Stm flow arbitration sig = Pimp
Fd flow arbitration sig = total error (fw demand)
Describe purpose of DFWCS valve linearization and sequencing logic?
What is sequence of valves opening on up power?
Open FRV and bypass valves based on
How does DFWCS control MFP speed?
Why designed like this?
@ higher flows, more head losses=>need more d/p to get fw to SG’s
@ lo flows, minimize erosion by lowering d/p
Inputs to Hi power mode of DFWCS?
Pimp - PT-505A,506A,8 (med select) - input to program lvl (old system ramp lvl) - arbitrator sig for steam flow Ls/g - LT-517,518,518 (med select) - vs. program lvl Tfw - TT-1189,1190,1191 (med select) - temp compensation for lvl error (shrink & swell) Fstm - FT-512,513 (arbitrated w/ Pimp) - vs. Ffw Ffw - FT-510,511 (arbitrated w/ total error) - vs. Fstm Ps/g - PT-514,515,516 (med select) - avg of all loops - density compensation for steam flow
Inputs to Lo power mode of DFWCS
Pimp - PT-505A,506A,8 (med select) - input to program lvl (old system ramp lvl) Ls/g (NR) - LT-517,518,518 (med select) - vs. program lvl Tfw - TT-1189,1190,1191 (med select) - temp compensation for lvl error (shrink & swell) Ls/g (WR) - LT-501 - anticipatory signal...?
Inputs to valve linearization & sequencing logic
Ps/g - PT-514,515,516 (med select) - all loops averaged - vs. Pfw for d/p signal Pfw - PT-508,508A,508B (med select) - vs. Ps/g for d/p signal