Circ Water Flashcards

(19 cards)

1
Q

How is CW used as a backup for Fire Protection

A
  • Fire truck or pump skid
  • Suction hose dropped into canal
  • Pump to fire header
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is drained/ returned to the CW Canal

A
  • Cond Demins Lo TDS Sump
  • SP Filter backwash sumps
  • Yard Area Sump
  • TB roof drains
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Where is CW Makeup and Blowdown controlled from

A
  • WRF control room
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the makeup rate to the CW canal

A
  • 18,000 gpm from evaporation
  • 2,000 gpm for blowdown
  • 20,000 gpm total
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the blowdown rate for CW, why do we blowdown, and where is it sent

A
  • 2000 gpm
  • Prevent excessive accumulation of solids
  • Evap ponds
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How many Fans are there per cooling tower

A

16

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How are cooling tower fans Indicated, how are they controlled

A

Indicated - PMUX

Controlled - PMUX, can operate brkrs locally

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Which Cooling Tower fan trip is bypassed while starting

A
  • High Vibration trip

- Bypassed for 30 seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How do you determined if a cooling tower fan tripped due to high vibration

A
  • Locally checked at breaker

- Blue light indicates vibe trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What are the power supplies for the CW pumps

A

A & B - NAN-S01

C & C - NAN-S02

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What permissives does a running CW pump provide

A
  • Acid Injection
  • Chlorine Injection
  • Tower Blowdown vlvs
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What are the CW pump Start Interlocks

A
  • Water Box outlet MOV Open

- Pump disch MOV Closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How long does it take vlvs to cycle in the CW system

A

Pump Disch. - 30 Seconds

Water Box Outlet - 60 Seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is CW vlv logic for starting the First CW pump in a loop

A
  • Pump starts

- MOV opens to 44%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is CW vlv logic for starting the Second CW pump in a loop

A
  • Pump starts
  • Associated MOV goes to 44%
  • 3 minute delay
  • associated MOV goes full open
  • 1st MOV goes full open
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is CW vlv logic for stopping the First CW pump in a loop

A
  • Disch MOV goes to 8%
  • Pump Trips
  • Disch MOV goes fully closed
  • 2 Minute interlock prevents restart
  • IF x-tie not open OR only 1 pump in opposite loop 2nd
    disch MOV will go to 44%
17
Q

What is CW canal level Normal, Min levels and why

A

CW pump minimum - 18’
PW pump minimum - 19’
Normal level - 22’3” - 23’3”

  • Prevents short circuiting tower air flow
18
Q

What are the CW pump limits for CW towers in/out of service

A

3 Towers - 4 pumps running
2 Towers - 2 pumps running
1 Tower - 1 pump running

19
Q

What off normal condition other than normal trouble alarm conditions will also cause a CW Sys Trouble alarm

A

CW-UV-11 x-tie vlv not in AUTO