How is CW used as a backup for Fire Protection
What is drained/ returned to the CW Canal
Where is CW Makeup and Blowdown controlled from
What is the makeup rate to the CW canal
What is the blowdown rate for CW, why do we blowdown, and where is it sent
How many Fans are there per cooling tower
16
How are cooling tower fans Indicated, how are they controlled
Indicated - PMUX
Controlled - PMUX, can operate brkrs locally
Which Cooling Tower fan trip is bypassed while starting
- Bypassed for 30 seconds
How do you determined if a cooling tower fan tripped due to high vibration
- Blue light indicates vibe trip
What are the power supplies for the CW pumps
A & B - NAN-S01
C & C - NAN-S02
What permissives does a running CW pump provide
What are the CW pump Start Interlocks
- Pump disch MOV Closed
How long does it take vlvs to cycle in the CW system
Pump Disch. - 30 Seconds
Water Box Outlet - 60 Seconds
What is CW vlv logic for starting the First CW pump in a loop
- MOV opens to 44%
What is CW vlv logic for starting the Second CW pump in a loop
What is CW vlv logic for stopping the First CW pump in a loop
What is CW canal level Normal, Min levels and why
CW pump minimum - 18’
PW pump minimum - 19’
Normal level - 22’3” - 23’3”
What are the CW pump limits for CW towers in/out of service
3 Towers - 4 pumps running
2 Towers - 2 pumps running
1 Tower - 1 pump running
What off normal condition other than normal trouble alarm conditions will also cause a CW Sys Trouble alarm
CW-UV-11 x-tie vlv not in AUTO