PLCS Flashcards

(23 cards)

1
Q

What is a potential concern when working on PLCS

A

A potential to initiate a unit trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What input does PLCS receive from RRS

A

Tave

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the Pzr LT power supplies

A

110x - PNA-D25

110y - PNB-D26

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the power supply FROM LT-110x/y to PLCS

A

110x - NNN-D12

110y - NNN-D11

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What automatic actions will PLCS provide to PPCS

A
  • actual level +3.0% above setpoint will cause htrs to
    energize in anticipation of an out surge
  • Level <25% trips all htrs off
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Where are LT 110x/y signal sent?

A

110y - RSP, Hi/Lo alarms, Hi/Lo deviation alarms

110x - Same, and PAM recorder

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the purpose of the PLCS Function Generator

A

Calculates a PZR level set point based on Tave from RRS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Describe how PZR level is controlled in relation to Tave, and power

A
  • Tave band 568-586*F equates to 15-100% power
  • PZR level increases Linearly from 15-100% power
  • PZR min set point level (15%) - 33%
  • PZR max set point level (100%) -52.6%
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the purpose/reasoning behind the PZR min/max levels

A

Insurge will not reach nozzles

Outsurge will not drain PZR on a trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the proper way to shift RCN-LIC-110 PZR level controller from R/A to L/A

A
  • Adjust L/A setpoint to match remote setpoint
  • Press Manual button
  • Place R/L switch to Local
  • Press the Auto button

Be in Manual when shifting R/L

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the different pointers on RCN-LIC-110 for

A

Red - Actuall PZR level
Black/White - Remote setpoint
Black - Local setpoint from thumb wheel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is required to make the PZR “Operable”

LCO 3.4.9

A

Pressurizer SHALL be Operable

  • Water level ≥27% and ≤56%
  • 2 groups of HTRS ≥125kw each

Mode 1-3
N/A transient levels

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What interlock is there between RRS and PLCS

A

RRS cannot be taken to test with RCN-LIC-110 in R/A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What are the Letdown flow limits when RCN-LIC-110 is in Automatic

A

30-135 gpm

30 - adequate CH flow preheat to minimize stress on
CH nozzle
135 - prevent exceeding max LD flow

Lag feature used to minimize sudden flow changes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What are the letdown flow limits when RCN-LIC-110 is in manual

A

0-150 gpm

Lag feature disabled

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When should the LD selector switch be in P/Q or Both

A
  • 1 LD control valve should be used above 1000psia
    increasing
  • 2 LD control valves can be in service below 1050 psia
    decreasing
    -2 LD control vlvs >1200 could exceed relief capacity
17
Q

How does PLCS control the always running CH pump

A

Always running, PLCS does not control

18
Q

How does PLCS control the Normally running CH pump

A
  • Normally running
  • +15% increasing of setpoint pump STOPS
  • +14% decreasing pump restarts

Must be in Auto After Stop

19
Q

How does PLCS control the STBY CH pump

A
  • Normally not running
  • -23% of setpoint Starts STBY pump
  • -14% of setpoint Stops STBY pump
20
Q

When do the PZR Hi/Lo level alarms come in

A

60%

25% - resets at 27%

21
Q

When do the PZR level Error alarms come in

A

+8.5% resets at 8.2%

-3.5% resets at -2.7%

22
Q

List PZR pressure settings and event

A
2750 psia - RCS Safety Limit
2500 psia - RCS Design Press.
2475 psia - PZR safeties open
2409 psia - SPLA HP B/U trip
2383 psia - HP Rx trip
2300 psia - Spray Full open
2295 psia - DNB LCO
2285 psia - PZR Hi press alarm/ cutout
2275 psia - Spray vlv begin to open
2250 psia - NOP
2225 psia - Prop htrs max, low press. reset
2200 psia - All htrs on, Low press. stpt. 
                     override blocked
2160 psia - Low Press alarm
1837 psia - LP Rx trip, SIAS, CIAS
23
Q

What are the CH pump different flag indications and how are controls different for each

A

Red Flag - Run; no PLCS control

Green Flag - Auto after Stop; PLCS controls