What is a potential concern when working on PLCS
A potential to initiate a unit trip
What input does PLCS receive from RRS
Tave
What are the Pzr LT power supplies
110x - PNA-D25
110y - PNB-D26
What is the power supply FROM LT-110x/y to PLCS
110x - NNN-D12
110y - NNN-D11
What automatic actions will PLCS provide to PPCS
Where are LT 110x/y signal sent?
110y - RSP, Hi/Lo alarms, Hi/Lo deviation alarms
110x - Same, and PAM recorder
What is the purpose of the PLCS Function Generator
Calculates a PZR level set point based on Tave from RRS
Describe how PZR level is controlled in relation to Tave, and power
What is the purpose/reasoning behind the PZR min/max levels
Insurge will not reach nozzles
Outsurge will not drain PZR on a trip
What is the proper way to shift RCN-LIC-110 PZR level controller from R/A to L/A
Be in Manual when shifting R/L
What are the different pointers on RCN-LIC-110 for
Red - Actuall PZR level
Black/White - Remote setpoint
Black - Local setpoint from thumb wheel
What is required to make the PZR “Operable”
LCO 3.4.9
Pressurizer SHALL be Operable
Mode 1-3
N/A transient levels
What interlock is there between RRS and PLCS
RRS cannot be taken to test with RCN-LIC-110 in R/A
What are the Letdown flow limits when RCN-LIC-110 is in Automatic
30-135 gpm
30 - adequate CH flow preheat to minimize stress on
CH nozzle
135 - prevent exceeding max LD flow
Lag feature used to minimize sudden flow changes
What are the letdown flow limits when RCN-LIC-110 is in manual
0-150 gpm
Lag feature disabled
When should the LD selector switch be in P/Q or Both
How does PLCS control the always running CH pump
Always running, PLCS does not control
How does PLCS control the Normally running CH pump
Must be in Auto After Stop
How does PLCS control the STBY CH pump
When do the PZR Hi/Lo level alarms come in
60%
25% - resets at 27%
When do the PZR level Error alarms come in
+8.5% resets at 8.2%
-3.5% resets at -2.7%
List PZR pressure settings and event
2750 psia - RCS Safety Limit
2500 psia - RCS Design Press.
2475 psia - PZR safeties open
2409 psia - SPLA HP B/U trip
2383 psia - HP Rx trip
2300 psia - Spray Full open
2295 psia - DNB LCO
2285 psia - PZR Hi press alarm/ cutout
2275 psia - Spray vlv begin to open
2250 psia - NOP
2225 psia - Prop htrs max, low press. reset
2200 psia - All htrs on, Low press. stpt.
override blocked
2160 psia - Low Press alarm
1837 psia - LP Rx trip, SIAS, CIASWhat are the CH pump different flag indications and how are controls different for each
Red Flag - Run; no PLCS control
Green Flag - Auto after Stop; PLCS controls