What is the primary purpose of QSPDS
Provide indications to detect:
Approach to, existence of, and recovery from
Inadequate Core Cooling ICC
(subcooling margin detector)
What parameters are used by QSPDS
What event caused the existence of QSPDS
Three mile island
How are QSPDS and ERFDADS connected
They are linked via QSPDS/ERFDADS data link that shares virtually all data
What are the power supplies to QSPDS
PNA-D25
PNB-D26
Isolation cabinets:
PNC-D27
PND-D28
What indicator is used to determine QSPDS is still working/running
A flashing square in the upper left corner
What parameters are monitored/displayed by QSPDS
Which QSPDS parameters are located on B02?
Values from Train A QSPDS
What specific temperature is trying to be maintained while monitoring/maintaining Adequate Core Cooling
Fuel cladding temperature of 2200*F
Which parameters are used to determine adequate core cooling
What are the only instruments that DIRECTLY measure coolant inventory loss
Heated Junction Thermocouples (HJTC’s)
What level is measured by HLTC’s and why
- its a direct measurement of level vs 2 phase calc.
How does HJTC’s measure water levels, what values are normal vs abnormal
Normal ▲T
- 90F
Void ▲T
- 200F OR unheated >700*F
Describe the layout of HJTC’s
2 Channels with 8 sensors/channel
What limitation exists with the Plenum HJTC’s
The plenum HJTC’s are invalid if any RCP’s are running
-RCP’s my cause mixed phase flow even if reduced
inventory
What is the range of CET’s
200-2300*F
What is required to make Post Accident Monitoring (PAM) “Operable” in regards to QSPDS
Modes 1-3
PAM instrument for each Function shall be operable
- 4/8 HJTC’s/ channel 2 upper and 2 lower
Where do HJTC’s enter the core
Through a spare CEDM nozzle in Rx vessel head