Condensate Flashcards

(20 cards)

1
Q

What is the minimum CW temperature for the Main Condensers and why

A

65*F

fatigue stress on tubes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the normal storage volume of the condenser hotwells

A

100,000 gallons

4 minutes of full flow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When do the condenser equalizing ducts blow

A

30*F differential temperature between shells

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

When do the condenser equalizing ducts blow

A

30*F differential temperature between shells

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When can you open the condenser vacuum breakers be opened

A

Main turbine <1200 rpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the power supply for Hotwell makeup vlvs

A

NKN-D41

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the normal Condenser Hotwell levels and why

A
  • > 41” - HDP trip lowers hotwell level 9”
  • <45” Draw off opens
  • 30” condensate pump trip
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How does the Hotwell makeup vlv fail

A

Loss of Power - Closed
Loss of Air - Closed
Lo-Lo CST lelvel - Closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What will Cause hotwell draw off vlv to Auto Close

A
  • Low MFP suction press
  • High hotwell conductivity
  • Can be Overridden
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What are the power supplies to the Condensate pumps

A

A - NBN-S01
B - NBN-S01
C - NBN-S02

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What worthless feature does the Condensate pump discharge vlvs have

A

Push to stop button to stop vlv travel mid cycle

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Which hotwells do the Condensate pumps suck off

A

A - 2A/B/C
B - Either
C - 1A/B/C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What are the Condensate pump trips

A
  • Low Flow - <3600 gpm for >45 seconds
  • Lo Hotwell lvl - <30” on both LT’s can override on A/C pumps for hotwell pump down
  • B only, suct vlv must be full open
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What are the power supplies to the Condensate pump mini-flows

A

A - NNN-D12
B - NNN-D11
C - NNN-D12

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

How do the Condensate mini-Flows fail what problem could that cause

A
  • OPEN loss of air or power

- Could result in Low MFP suct. press.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What signals are provided by CDN-V191 Condensate Demin Inlet isolation

A
  • Open Permissive for 199 Demin outlet

- Modulate Permissive for 195 Demin bypass

17
Q

How large of a CW leak can Condensate Demins control/ handle

18
Q

When does the Condensate Demin Bypass vlv open

A
  • Inlet and Outlet vlvs open

- D/P >55 psi

19
Q

How does the Demin Bypass vlv CDN-V195 fail/ Auto actuate

A
  • Fails OPEN loss of air or power

Auto Opens

  • Demin Inlet or Outlet NOT full open
  • High D/P 55 psid
  • Low Air press. 90 psig
20
Q

When can long path recirc isolation vlv SGN-HV-46 be opened and how is that accomplished and why

A
  • <200*F
  • Manual bypass vlv around isolation
  • Prevents Thermal shock/ water hammer