What will Auto start the DG’s
SLAC
SIAS
LOP
AFAS
CSAS (test mode)
What is the rating of the DG
5500 kw continuous
6050 kw for 2 hours in a 24 hour period
How quickly must a DG start
At rated speed and voltage AND ready to accept load within 10 SECONDS
What is the ONLY direct mechanical trip of the DG
Overspeed butterfly valve
What is the ONLY automatic trip to stop the DG on loss of Control Air
Overspeed butterfly valve
What is the minimum level of the FOST
Describe the operating characteristics of the Fuel Oil Transfer pump
What is the minimum level in the DG Day tank
How much fuel does the DG use at full load
6.55 gpm
Describe the DG main governor
How does the DG governor control engine speed
How is a DG “Slow Start” accomplished
What is a DG Incomplete Sequence Trip
How does the DG Overspeed Governor work
What does DG Jacket Water cool
How is flow directed from the Engine Driven Jacket water pump
How is flow directed from the Motor Driven Jacket water pump
What concern/ OE is there with the DG Jacket Water Heater
- Heater will be damaged if run without water
Describe the flow of the engine driven Lube Oil
Describe the flow of the engine driven Lube Oil
How does a low DG lube oil pressure trip work
What are the DG Turbo low oil setpoints
Alarm - 30 psig
Trip - 27 psig
What starts the DG Essential HVAC
How Long can the DG run without ESP support
Unloaded - 15 minutes
Loaded - 2.6 minutes