Stator Cooling Flashcards

(21 cards)

1
Q

How does Stator cooling water enter/leave the main generator and why

A
  • Enters and leaves Generator from above
  • ensures Generator stays full is stator cooling lost
  • Lines also have vacuum break to prevent siphoning
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How does Stator cooling water enter/leave the main generator and why

A
  • Enters and leaves Generator from above
  • ensures Generator stays full is stator cooling lost
  • Lines also have vacuum break to prevent siphoning
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How is Hydrogen removed from Stator Cooling water

A
  • Cooling leaving generator maintained atm. press.
  • Line leaving generator is much larger than supply
  • Stator cooling water tank vented to atm.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How is Stator cooling water system affected by a loss of NKN-D41

A
  • Tripping power is lost
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What does Stator Cooling Water cool

A
  • Stator
  • Connector Ring
  • Terminal bushings
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What causes a Stator Cooling Water stby pump to start

A
  • Low Disch press. 581 gpm

- LoLo Disch press. 549 gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What will Cause Stator Cooling Water pump trips

A
  • Electrical Fault
  • Generator Differential
  • Stator Ground
  • Unit Differential Lockout
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the capacity of the Stator Cooling HX’s

A
  • Each HX approx. 80%

- 1 HX lost reduce power to 80%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What temperature does Stator Cooling water maintain

A

42*C leaving the HX’s

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the concern if Stator Cooling Water conductivity is too high

A
  • Flashover within Generator
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

When is Stator Cooling Water Resin changed

A
  • 24 Months
  • press drop of 15 psi
  • Conductivity > 0.5 micromhos/com
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the purpose of the Stator cooling Water pressure control vlv

A
  • Max press 28 psig
  • Min press 22 psig
  • Ensures bubbles or gas in stators are purged
  • Prevents exceeding value req’d at full load
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

When is SLMS started

A
  • After Main Generator is Synched to the grid
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the Main Generator output limited to without Isophase bus cooling

A
  • 23,000 amps

- Full load can be maintained for 30 minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the Main Generator output limited to without Isophase bus cooling

A
  • 23,000 amps

- Full load can be maintained for 30 minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What are the Isophase bus temperature limits

A

Iso Buses - 105C
Enclosures - 80
C
- If exceeded lower generator load

17
Q

How is Isophase bus cooling controled

A
  • Manually throttle cooler outlet vlvs (TC)
  • Air inlet temp maintained < 130*C
  • If cooler removed from svc close inlet vlv
18
Q

What actions are required if H2 is detected in Isophase bus

A

Hi Alarm - Reduce H2 press in Generator

HiHi Alarm - Remove Generator from svc.

19
Q

What can be done if Isophase bus cooling is lost

A
  • A portable unit can be used instead
20
Q

What Stator Cooling Water conditions will cause a Turbine Trip

A
Low Inlet water press  - 549 gpm 
Stator Inlet Flow           - 549 gpm
Connecting Ring flow  - 85 gpm
High Outlet Temp         - 85*C
Gen bushing low flow  - 64 gpm 
  • 70 Second Time Delay for all
  • 2/3 logic for all
21
Q

At what Stator Cooling Water conductivity must an Operator Trip the Generator

A

> 9.9 micromho/cm