What is the Capacity of the CST
550,000 gallons
What is the allowed temperature band of the CST and why
40 - 120*F
- minimum to prevent SG thermal shock
Where does the Hotwell makeup tap into the CST
> 330,000 gallon level
- Provides 3 days of normal operation
Where does the Hotwell makeup tap into the CST
> 330,000 gallon level
- Provides 3 days of normal operation
What will Auto Start CT pumps
SLCC
What is the Minimum operating level of the CST
31 feet
When does the CST Empty Alarm come in
What is required for CST level indication to be OPERABLE
Mode: 1-3
2 CST level transmitters operable
- Outputs to QSPDS
What is the minimum level for the CST to be OPERABLE
Modes: 1-3, 4 when SG used for heat removal
> 29.5 feet
What is the CST minimum tech spec level based on
How is AFN vs AFA/B when CST is unavailable
- AFN cannot swap, remains INOP