1
Q

What type of detector is used for the Gas Process Monitors?

A

Beta scintillation detector for low range detection
When high range detection is needed a GM detector is used

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What type of detector is used for the Liquid Process Monitors?

A

Gamma scintillation detector for low range detection.
When high range detection is needed a GM detector is used

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What automatic actions occur on a Trip 2 signal on (1EMF-15, 2EMF-4) Fuel Storage Pool Area?

A

Automatically stops new fuel elevator from being raised

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What automatic actions occur on a Trip 2 signal on (1EMF17, 2EMF-2) - Reactor Building Refueling Bridge?

A

Actuates containment evacuation alarm below P-6. This auto action is blocked when both source ranges’ high flux trip is blocked.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What automatic actions occur on a Trip 2 signal on 1(2) EMF31 - Turbine Bldg. Sump?

A

Stops automatic and manual operation of the sump pumps in the unit related sump.
An override switch on local sump pump control panel allows manual operation of the pumps.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What automatic actions occur on a Trip 2 signal on 1(2) EMF33 - Condenser Air Ejector Exhaust?

A
  • Closes SG BB flow control valves 1(2)BB-24, 65, 69, & 73
  • Closes SG sample isolation valves 1(2)NM-269, 270, 271, & 272
  • Closes 1(2) EMF-34 inlet isolation 1(2)NM-267
  • Closes BB discharge to the Turbine Building sump 1(2)BB-48
  • Closes BB tank vent to atmosphere 1(2)BB-27
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What automatic actions occur on a Trip 2 signal on 1(2) EMF35/36L Unit Vent Particulate/Gas Monitor?

A
  • Trips unit related VA Unfiltered Exhaust Fans A and B (Bypassed if VC/YC in LOCAL)
  • Aligns the unit related VA Filtered Exhaust Units A and B to Filter Mode
  • Aligns VF to Filter Mode
  • Closes 1WG-160 (Unit 1 only)
  • Closes 1(2) VQ-10
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What automatic actions occur on a Trip 2 signal on 1(2) EMF38 - Containment Particulate?

A
  • If below P-6, the containment evacuation alarm is actuated.
  • The Containment Ventilation Isolation (Sh) signal is actuated if at least one train of SSPS is in service.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What automatic actions occur on a Trip 2 signal on 1(2) EMF39 (L) - Containment Gas - Low Range?

A
  • If below P-6, the containment evacuation alarm is actuated.
  • The Containment Ventilation Isolation (Sh) signal is actuated if at least one train of SSPS is in service.
  • A High Radiation signal shutdowns VP (separate from the Sh signal)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What automatic actions occur on a Trip 2 signal on 0EMF41 - Aux Bldg Ventilation?

A
  • Places both units VA Filter Exhaust in filter mode by closing the VA filter bypass dampers.
    *The Trip 2 must be reset to realign VA back to bypass.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What reading on 0EMF41 - Aux Bldg Ventilation would require conduct a site assembly?

A

> 1x10^6 CPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What automatic actions occur on a Trip 2 signal on 1(2) EMF42 – Spent Fuel Pool Ventilation?

A

Aligns VF to filter mode

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What automatic actions occur on a Trip 2 signal on 0EMF49 (L) - Liquid Waste - Low Range?

A

Closes 1WL-124 (Waste Monit Tnk Pmps Disch)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What automatic actions occur on a Trip 2 signal on 0EMF50L - Waste Gas Discharge - Low Range?

A

Closes 1WG-160 (WGDT Outlet to Unit Vent Isol)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What automatic actions occur on a Trip 2 signal on 1EMF52 – Clean Area Floor Drain?

A

Realigns Floor Drain Sump D(C) Pump discharge from the turbine building sump to the ND & NS room sump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What automatic actions occur on a Trip 2 signal on 1(2) EMF53A & B – Containment Train A(B)?

A

1(2) EMF-53A –
- Closes 1(2) WL-825A (Cont Sump Pmps Disch Cont Isol)
- Closes 1(2) WL-867A (VUCDT Cont Isol)
1(2) EMF-53B –
- Closes 1(2) WL-827B (Cont Sump Pmps Disch Cont Isol)
- Closes 1(2) WL-869B (VUCDT Cont Isol)

17
Q

What automatic actions occur on a Trip 1 signal on 1(2) EMF54HH – Unit Vent Gamma Hi-Hi Range?

A

Trips the 1(2) EMF35 & 36 sample pump

18
Q

What automatic actions occur on a Trip 2 signal on 0EMF-55 A & B - Tech Support Center Monitor?

A

Isolates TSC outside air intakes by closing

19
Q

What automatic actions occur on a Trip 2 signal on 0EMF-57 - Waste Monitor Tank Building Liquid Discharge Monitor?

A

Closes 1WL-X28 (MTB Disch to RL Isol)

20
Q

If 1(2) EMF53A & B – Containment Train A(B) are non-functional, how is containment radiation measured?

A

RP would monitor the contact dose rate at the center of the outside airlock door.