VI, VS, VB Flashcards

(31 cards)

1
Q

What is the purpose of the VI system?

A

Supplies dry, oil free, compressed air for instrumentation and control to various components of both units.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the purpose of the VS system?

A

Supplies low pressure compressed air for air operated tools, miscellaneous equipment, and various maintenance purposes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the purpose of the VB system?

A

Supplies clean, oil free, compressed air to various locations in the Auxiliary Building, Monitor Tank Building, and Containment for breathing protection against airborne contamination while performing certain maintenance and cleaning operations.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What happens when VI pressure reaches 96 psig?

A

If ASC is controlling, an individual compressor will start loading

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What happens when VI pressure reaches 94 psig?

A

If Centac Microcontroller is controlling, a standby compressor will start (“Hot Restart”)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What happens when VI pressure reaches 85 psig?

A

1VI-487 and 1VI-488 (Dryer Purge Exhaust Mufflers) close

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What happens when VI pressure reaches 80 psig?

A

-1VI-670 “VI Dryer Auto Bypass” opens.
-1VI-500 “VI supply to VS” closes.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What happens when VI pressure reaches 76 psig?

A

1VS-78 “VS supply to VI” opens

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the power supply to “E” VI compressor?

A

1LXI (Blackout Load Center)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the power supply to “F” VI compressor?

A

2LXH (Blackout Load Center)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the power supply to “D” VI compressor?

A

2SLXC (Shared Load Center)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Which VI compressors can get backup cooling from the RF system if KR cooling is lost?

A

E and F VI compressor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

At what VI pressure will the Reactors be tripped?

A

55 psig per AP/0/A/5500/022 (Loss of VI)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What system supplies the normal cooling water to the VI compressors?

A

KR (Recirculated Cooling Water

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

When the Backup Diesel Air Compressor are placed in service, where does the compressor discharge connect to the VI system?

A

Downstream of the VI dryers.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When does the Base VS compressor start?

A

Starts 90 psig
Unloads 100 psig

17
Q

When does the Standby VS compressor start?

A

Starts at 85 psig
Unloads at 95 psig

18
Q

What system cools the station air compressor oil coolers?

A

Recirculated Cooling Water (KR)

19
Q

What system cools the VS compressor aftercooler?

A

Conventional Low Pressure Service Water (RL)

20
Q

What are the power supplies to the VS compressors?

A

VS Air Compressor A 1SLXC
VS Air Compressor B 2SLXC

21
Q

What signal closes VI-77B (VI CONT ISOL)?

22
Q

What signal closes VI-312A (VI TO VP CONT ISOL)?

23
Q

What signal closes VS-54B (VS CONT ISOL)?

24
Q

What system supplies air to the Main Turbine bearing deluge system?

25
What system cools the VB compressor aftercoolers?
Service Building Chilled Water (YW) System
26
What system cools the VB compressor oil coolers and the heat exchangers associated with the dryer?
Recirculated Cooling Water (KR) System
27
What signal closes VB-83B (VB CONT ISOL)?
St
28
What are the VB compressor trips?
-High compressor discharge temperature - 235 degrees F -High discharge pressure - 135 psig -Dryer failure - Low evaporator pressure or high condenser pressure -High carbon monoxide - 10 ppm -Low KR pressure - 10 psig Motor Overload
29
What are the VB compressor power supplies?
VB Air Compressor A Motor - SMXU VB Air Compressor B Motor - SMXS
30
When does the VB compressor i the "BASE 1" mode start?
Starts at 95 psig Unloads at 105 psig
31
When does the VB compressor i the "BASE 2" mode start?
Starts at 85 psig Unloads at 95 psig