What is the purpose of the KR system?
A closed Loop Cooling System which supplies cooling water to non-safety equipment throughout the plant.
Power supplies to the KR pumps?
KR Pump A 1SLXC
KR Pump B 2SLXC
KR Pump C 1SLXD
When does the standby KR pump auto start?
When header pressure decreases to 40 psig
What is the minimum flow for the KR pump?
1000 gpm provided by 1KR16 (KR PUMP RECIRC CONTROL) which opens at 70 psig.
How is make-up to the KR storage take performed?
Manually from Demineralized Water (YM).
What system does KR supply cooling water to in the Auxiliary building?
NF system
How many KR HXs and pumps are normally in service?
3 Heat exchangers
2 pumps
At what level does annunciator 1AD-8 B-6 (KR Storage Tank Lo Level) come in at?
45%