What are CCW design temperatures and pressures?
What is the functional requirement of CCW post-DBA?
Cooling to SDC system to have within 24 hours a containment pressure 50% or less of the design pressure.
What removes heat from the CCW Heat Exchangers?
‘A’ Critical Service Water Header
What are the CCW Temperature Control Valves?
What is the purpose, design and capacity of T-3, CCW Surge Tank?
What is normal operating level of T-3?
47% - 74%
Where is T-3, CCW Surge Tank vented?
At what pressure does T-3, CCW Surge Tank relieve?
20 psi lifts RV-0915 - goes to waste gas collection header.
What supplies T-3, CCW Surge Tank?
T-81, Primary System Makeup Storage Tank.
What are CCW Heat Exchanger DP limits?
Maximum allowable flow through the shell side of the CCWHX is 4700 gpm each.
This corresponds to a ΔP across the CCWHX of:
What are the CCW pump minimum discharge pressure limits with one pump operating and one heat exchanger?
115 psig
What are the CCW pump minimum discharge pressure limits with one pump operating and two heat exchangers?
102 psig
What are the CCW pump minimum discharge pressure limits with two pumps operating and two heat exchangers?
115 psig
What are the CCW pump minimum discharge pressure limits with three pumps operating and two heat exchangers?
129 psig
What happens to CCW on SIAS?
What happens to CCW pumps on SIAS with loss of offsite power?
What happens to CCW on CHP?
CV-0910 CCW to Containment and CV-0911/CV-0940 CCW from Containment get a close signal.
Will Close if in AUTO
Will remain open if in OPEN
Will open if in AUTO and CHP reset
What happens to CCW on RAS?
On loss of DC to SV-0945/0946 what happens?
CV-0945/0946 CCW inlets fail open on loss of air.
What controls CV-0821/0822?
What are CV-0937 & CV-0938?
CV-0937 & CV-0938
What is CV-0944A?
CV-0944A
What is CV-0944?
CV-0944
What is CV-0977B
CV-0977B