What is the purpose of the Steam Generator Water Level Control system?
To regulate steam generator feedwater flow such that
Maintains indicated steam generator level above the Low Steam Generator Level trip setpoint (25.9%) and below the High Level Override setpoint (84.7%) for:
What is the steam generator water level control operational design?
Uses three elements of control:
Processed within Main Feed Reg Valve Level Indicating Controllers, LIC‑0701, LIC‑0703
SGWLC is “Level Dominant” signal is determined based on the S/G Level error (Actual level vs. Setpoint) as measured in the downcomer region
This signal is fine tuned via
How does the Automatic Control within LIC-0701/0703 function with the feed pumps and Main Feedwater Regulating Valves to control level?
Signal based on SG water level in downcomer, modified by mismatch between feed flow and steam flow.
Signal Sent to:
The feedwater regulating valve controller in combination with the turbine driver speed control system will function to control the level in each steam generator by modulating the feedwater flow.
Normal operating level (setpoint) is 65% at power
How does the MFP speed control HIC-0525 function within the SGWL system?
HIC-0525, when in cascade, selects the signal via LIC-0701/0703 from the steam generator requiring the higher feedwater flow which is compared to a feedback signal from turbine speed in the speed controller of each driver.
Any difference between the two signals will cause the speed controllers to produce a change in turbine speed in the appropriate direction.
How does MFP fixed speed control function with SGWL?
At low power levels (< 25% power) a single element control unit (Individual Pump Speed Controller) is used.
How do Main Feed Reg Valve Level Indicating Controllers, LIC‑0701, LIC‑0703 function?
Use steam generator water level in downcomer region as primary signal source.
Output signal refined by mistmatch between steam flow and feed flow.
Indications
Operating Modes
To transfer from manual to auto
Large feedwater transients are minimized by controller design which limits how quickly the output signal is generated when controller is in Auto and the setpoint is changed
How do Main Feed Reg Bypass Valve Level Indicating Controllers, LIC‑0734, LIC-0735 function?
Identical to LIC-0701 and LIC-0703, except
What is the purpose of the Main Feed Reg Bypass Valves, CV-0734, CV-0735?
Main Feed Reg Bypass Valves, CV-0734, CV-0735
Valves fail “as is” on loss of air.
What is the function of the Combined Speed Hand Indicating Controller, HIC-0525?
Combined Speed Hand Indicating Controller, HIC-0525
Modes of Operation
Indications
SV- Setpoint Variable
MV- Manipulated Variable (value of output meter
In order to use this controller to control pump speed, individual pump controller(s) (HIC-0526 and/or HIC‑0529) must be in CASCADE.
How do Main Feed Pump Speed Hand Indicating Controllers, HIC‑0526, HIC-0529 function?
Designed to control Main Feed Pump Turbine speed between 3250 to 5250 RPM. On Governor only.
Tuned to ensure pumps respond slowly to signal changes from the Combined Speed Controller, HIC‑0525.
If a rapid change in pump speed is called for, the Operator must place the individual pump controllers in MANUAL and use the slide bar at the bottom of the controller to change pump speed
Modes of Operation
Indications
What is the design function of the Main Feed Reg Valves, CV-0701, CV-0703?
Main Feed Reg Valves, CV-0701, CV-0703
What is the function of the S/G Level Transmitters, LT-0701, LT-0703?
S/G Level Transmitters, LT-0701, LT-0703
Control Channels
What is the function of the S/G Level Transmitters (LT-0758A/B, LT‑0757A/B)
S/G Level Transmitters (LT-0758A/B, LT‑0757A/B)
Primary use is during transients involving low S/G levels (<0% level) and when the PCS is cold
What is the function of Steam Flow Transmitters, FT-0702, FT-0704?
What happens if the pressure signal to the steam flow transmitters fails high or low?
Steam Flow Transmitters, FT-0702, FT-0704
Pressure signal fails low, indicated flow will decrease to a lower value.
Pressure signal fails high, indicated flow will increase to a higher value.
Due to changes in pressure causing changes in density without a corresponding change in sensed DP.
How does CHP interact with the SGWL control program?
Containment High Pressure (CHP)
What is the function of the Steam Flow Transmitters, FT-0702, FT-0704?
What is the function of Feed Flow Transmitters, FT-0701, FT-0703?
How does a dp flow transmitter work?
Feed Flow Transmitters, FT-0701, FT-0703
Flow rate is directly proportional to the square root of the differential pressure
How does Low S/G Pressure interact with SGWL?
Affects FRVs and FRV Bypasses
The FRV and FRV bypass close only on the S/G with the low pressure
How does High Level Overide affect SGWL?
High Level Overide
What is the purpose of the high level overide?
Prevent moisture carryover to the turbine which could possibly result in turbine damage.
How does a Turbine Trip affect SGWL control?
How do LIC-0701 and LIC-0703 react to a CHP, Low SG Pressure and High Level SG ground?
What are the power supplies for A SGWL components?
Most ‘A’ SGWLC equipment is normally powered from EY-10 and will automatically transfer to EY-30 on loss of EY-10, and will transfer back when power restored.
What are the power supplies for B SGWL components?
Most ‘B’ SGWLC equipment is normally powered from EY-20 and will automatically transfer to EY-40 on loss of EY-20 and will transfer back when power restored.