Explain the purpose of the Control Room HVAC System
Maintain the
Suitable for continuous personnel occupancy and reliable equipment operation under all conditions
Is the control room HVAC safety related?
NO
What are the functional capability and design features of the CRHVAC?
What components make up the over overall CRHVAC system?
Two trains of
What are the major components of the ‘A’ train of CRHVAC?
Air Handling Unit V‑95
Condensing Unit VC-11
Continuous Air Monitor Unit RIA-1818A
Charcoal Filter Unit VF-26A
Fan V-26A.
What are the major components of the ‘B’ train of CRHVAC?
How does Recirculation Mode for CRHVAC impact RIA-1818A/B’s monitoring capability?
RIA-1818A/B are not located in the recirculation flow path thus will not detect adverse radiological conditions.
How does Recirculation Mode for CRHVAC impact pressure in the Control Room Envelope?
CRE will depressurize due to lack of makeup air.
How is Recirculation Mode initiated?
Initiated by placing DPIC-1659 (DPIC-1660) in manual and closing Damper D-2 (D-9).
What is the normal flow path for CRHVAC?
What is the recirculation flow path?
What is the flow path for purging?
What is the Emergency Flow Path?
How do CHP and CHR impact CRHVAC?
CHP (2 of 4 at 4 psig)
CHR (2 of 4 at 10R)
Explain why a positive pressure is maintained in the Control Room, Viewing Gallery, TSC, and Mechanical Equipment Room.
Prevents airborne radioactive material from entering the controlled area subsequent to accidents.
Differential Pressure Transmitter DPT-1659 (DPT-1660)
What is the design and operation of Air Handling Units V-95 (V-96)?
Each air handling unit consists of the following
What are the power supplies to V‑95/96?
MCC-25
MCC-26
What is the function and power supply for VH-12/13, CRHVC Humidifiers?
What makes up V-26A/B, Emergency Air Filtration Units?
Each Air Filtration Unit consists of the following components:
What is the function of VF-26A/B’s electric heater?
What is the purpose of the charcoal filters within the Emergency Air Filtration Units VF-26A (VF-26B)?
Minimizes exposure to radioactive materials during accident conditions
What detects fire in the charcoal beds?
Charcoal bed temperature can be monitored at Charcoal Filter Fire Alarm Panel
Dual meter indicates temperature for upstream and downstream charcoal beds.
What is the design, capacity and power supplies for VF-26A/B, Emergency Handling Filter Fans? What starts them?
2 Stage Centrifugal Fan
Power Supply
Automatically started by CHP/CHR
What is the power supply and design of VC-11 and VC-10?
MCC-25
MCC-26
Skid mounted 4-cylinder compressors with condensers
Capacity – 554,400 BTU/HR = 46.2 tons of refrigeration
60 Hp motor