What is EDG rated output?
What Air Start System setpoints for operability and normal ranges?
For the Lube Oil System, describe its operational design basis and the normal operating range.
For the Fuel Oil System, describe its operational design basis and the normal operating range.
Provides storage of an adequate fuel supply,
The engine system normal operating pressure is between 40 psig and 60 psig.
For the Jacket Cooling Water System, describe its operational design basis and the normal operating range.
For the Turbocharger, describe its operational design basis and the normal operating range.
Uses hot exhaust gases to drive a turbine that takes in fresh air, compresses it (15 to 24 psig), and forces the air into the cylinders on the intake stroke. Exhaust temperatures (loaded) reach approximately 1200°F. To prevent heat damage to the turbocharger and to ensure cool air is discharged into the intake manifold, jacket water and lube oil are piped to the turbocharger. At full rated load and speed, the maximum allowable turbocharger inlet exhaust gas temperature is 1350°F
For the NSD/DBA Sequencers, describe its operational design basis and the normal operating range.
What is the 1-1 EDG Output Breaker?
152-107
What is the 1-2 EDG Output Breaker?
152-213
What are the features of the Emergency Diesel Generator Output Breaker Interlocks for manual operations?
What are the features of the Emergency Diesel Generator Output Breaker Interlocks for automatic operations?
What lockout protection is provided to the Emergency Diesel Generator output breakers?
Lockout protection is provided to preclude auto-closure of the EDG breaker to a faulted bus. The bus lockout protection initiates when the normal supply (Station Power/Safeguards) breaker trips on overcurrent. The EDG will automatically start on an undervoltage signal but the overcurrent trip will block the EDG breaker automatic closure until the overcurrent lockout relay has been manually reset.
What is the Woodward Governor mechanical subsystem for speed/load control for the Emergency Diesel Generator?
What is the Woodward Governor electrical subsystem for speed/load control for the Emergency Diesel Generator?
What is the Unit Control Mode of the Woodward Governor electrical subsystem for speed/load control for the Emergency Diesel Generator?
What is the Parallel Control Mode of the Woodward Governor electrical subsystem for speed/load control for the Emergency Diesel Generator?
What is Speed Droop Control?
(a) The voltage droop mode prevents the generator from carrying too much reactive load in the over-excited or under-excited mode with respect to the infinite bus (grid).
What are the EDG 187 Relays?
Three (187) differential relays (one per phase) are connected to current transformers, one set on the neutral side of the generator windings and the other set on the bus side of the 2400V EDG incoming circuit breaker.
This arrangement protects the generator, generator incoming circuit breaker and the power cables against faults in this zone.
The relays trip the 2400V EDG breaker via lockout relay (186) and shut down the diesel engine via the shutdown relay (SDR).
What are the EDG 151 Relays?
Three inverse time overcurrent relays (151) are connected on the generator side of the EDG 2400V breaker to protect the EDG circuit from overloads.
They function by tripping the EDG breaker via lockout relay (186) and shut down the diesel engine via the engine shutdown relay (SDR).
The relays provide an alarm at 100% of the generator nameplate loading and trip the generator at 110% of the nameplate rating, based on 3125 KVA at 80% power factor.
The overcurrent trip logic is a two out of three (2/3) coincidence.
Trip Setpoint is 824 amps.
What is Incomplete or Cranking Failure Start for the EDG?
Describe the consequences of operating the Emergency Diesel Generators under improper temperature, pressure or flow parameters (water, air, oil)
If lube oil pressure <= 40 psig and EDG not tripped, then trip it.
If lube oil pressure DP > 20 psid, then EDG in operable. If conditions allow, shut down unit.
If lube oil temperature >= 200F with no service water, then trip it. Otherwise unload and secure if plant conditions permit. If less than 90F then EDG in operable.
If raw water pressure <= 25 psig and loss of service water, then trip the diesel. If operation required, maintain JW Temp <195F and Oil <205.
JW pressure less than 10 psig trips off crankcase exhausters and requries unit shut down if other power available.
If JW temperature >= 195 or <=95, then EDG in operable. If conditions permit, unload and stop.
If starting air pressure < 95 psig on two indicaters, EDG is inoperable.
Describe the consequences of operating the Emergency Diesel Generators in an under excited condition.
Excessive reactive load can result in generator high currents and over-heating. When the rotor field excitation is less than that required, leading reactive current flows in the generator stator windings. These flows in the generator stator winding can cause the stator end-turns can overheat, this leads to insulation damage. If left unchecked, the rotor field strength can weaken to the point that the generator could “slip a pole”. This causes catastrophic failure of the coupling between the prime mover and the generator, and sometimes worse
Describe the consequences of operating the Emergency Diesel Generators in an over excited condition.
Over excitation of a generator causes saturation of the magnetic core of the generator, and stray flux may be induced in non-laminated components that are not designed to carry flux. Excessive flux may also cause excessive eddy currents in the generator laminations that result in excessive voltages between laminations. This may cause severe overheating in the generator or transformer and eventual breakdown in insulation”
Describe the consequences of closing a breaker between buses with unmatched frequency or voltage.
Sync Check should not allow it. Generator/breaker damage is result.