Is the shield cooling system safety related and what is its purpose?
Not safety related.
Closed loop cooling system
Removes heat from the biological shield surrounding the reactor vessel thereby limiting stresses in the structural concrete.
What is the design function of the shield cooling system?
Maintains structural concrete temperature less than 165°F
Maximum normal heat load on the system at full power is 120,000 BTU/hr.
P-77A/B, Shield Cooling Pumps
P-77A/B, Shield Cooling Pumps
Capacity - 180 gpm each (100%)
Discharge Pressure –approximately 61 psig
P-77A from MCC 2
P-77B from MCC 1
P-77A/B auto starts how?
Pump control switch in “Pull to Standby”
PS-0935 at 35 psig starts pump
E-64, Shield Cooling Heat Exchanger
E-64, Shield Cooling Heat Exchanger
Heat Removal - 200,000 BTU/hr
Shell - CCW
Tube - Shield Cooling Water
HX outlet butterfly valve (MV-CC106) is manually throttled to control system temperature.
Shield Wall Cooling Coils
Shield Wall Cooling Coils
Two sets of coils with 3 coil sections in each set
Design Pressure – 75 psig
Design Temperature – 200°F
Normal flow rate is 38 to 43 gpm per coil section and 134 to 154 gpm per coil set (wall section + slab section = coil set).
CV-0932 & CV-0934, Coil Inlet Supply Valves
CV-0932 & CV-0934, Coil Inlet Supply Valves
Air operated, fail open diaphragm valves
C-08/03
Interlocked with associated flow alarm so that when valve is closed, low flow alarm is bypassed
What does the shild wall coil relieve at?
Each wall coil has a relief valve for overpressure protection due to thermal expansion (100 psig)
What are the flow indications for wall coils?
FI-0928, FI-0929, FI-0931 for A Coil
FI-0934, FI-0935, FI-0936 for B Coil
What temperature indications are there in the control room?
TE-0931 (TE-0933) – provides control room indication
High temperature alarm at 120°F via TIA-0931 (TIA-0933)
What alarms on low flow?
FS-0932 (FS-2104) – provides control room alarm when in-service coil flow decreases to ≤ 80 gpm
Alarm bypassed when inlet supply valve CV-0932 (CV-0934) is closed.
What is the design of the Floor Slab Coils?
Two sets of coils with each having 1 section
Design Pressure – 75 psig
Design Temperature – 200°F
Normal flow rate through floor coil is 20 to 25 gpm
Local flow and temperature indication
T-62, Shield Cooling Surge Tank
T-62, Shield Cooling Surge Tank
Maintains positive suction head on Shield Cooling Pumps.
Provides surge volume for Shield Cooling Water expansion and contraction.
Provides a point for the addition, recirculation and sampling of chemicals for the system.
CV-0927 Shield Cooling Surge Tank Makeup Valve
CV-0927 Shield Cooling Surge Tank Makeup Valve
Air operated diaphragm valve – fails closed
Level Switch (LS-0927) controls tank level
Makeup supplied from T-81, Primary System Makeup Water Tank
CV-0939 Containment Isolation
CV-0939 Containment Isolation
C-13 by two-position OPEN-CLOSE control switch
Automatically closes on Containment High Pressure (CHP) or Containment High Rad actuation (CHR)
EK-1303, “REACTOR SHIELD CLG LO FLOW”
EK-1303, “REACTOR SHIELD CLG LO FLOW”
EK-1302, “REACTOR SHIELD CLG PUMPS DISCH LOW PRESS
EK-1302, “REACTOR SHIELD CLG PUMPS DISCH LOW PRESS
EK-1301, “SHIELD CLG PUMPS TRIP
EK-1301, “SHIELD CLG PUMPS TRIP
EK-1304, “REACTOR SHIELD CLG HI TEMP”
EK-1304, “REACTOR SHIELD CLG HI TEMP”
EK-1305, “SHIELD CLG SURGE TANK T-62 HI LO LEVEL”
EK-1305, “SHIELD CLG SURGE TANK T-62 HI LO LEVEL”
SOP-29 Requirements
SOP-29 Requirements
Shield Cooling System shall be in operation prior to PCS temperature exceeding 165°F
Minimum flow
Maximum system flow
Flow Balancing