What makes a fire barrier operable?
How do non-functional fire barriers get handled?
When a fire, sub-volume, and/or exterior wall barrier is non-functional the Shift Manager shall:
What is Defense in Depth?
Typically piping arrangement to the sprinklers and hose stations is such that no single failure would render both systems unavailable. Where is this not done?
One exception is the water supply to the Charging Pump Room sprinklers
Line break could cause loss of both the sprinklers and hose station
What is a fire barrier?
What are the actions associated fire detection and or protection out of service within a High Safety Significant Area?
When a Fire Detection System in a HSS area is non-functional:
If Door 167B, Scuttle Hatch From CCW Room to “West” ESG is open, what must be functional?
If in Mode 1, 2 and 3
Auxiliary Feedwater Pump P-8A shall be OPERABLE
What must be done if Door 167,CCW Room to 590 Corridor is blocked open?
Floor Plugs to be in place in Door 167 is Open
What are the type of fire dectors utilized here?
If the required fire protection equipment is non-functional (i.e., required fire fighting equipment missing or defective) what must be done?
The non-functional fire protection equipment shall be replaced within one (1) hour OR
Additional fire hose capable of reaching the unprotected area shall be provided within one (1) hour at an functional fire hose reel station, fire hose rack, or fire hydrant hose house.
What are the effects of water spray on electrical equipment?
To prevent potential of electrical shock maintain maximum distance while still maintaining spray on fire
All nozzles used within the plant (with the exception of hydrant houses) are electrically safe fog type nozzles
Nozzles are pinned to prevent opening beyond the 30° position thus maintaining fog spray
What is the output and pressure of the fire pumps?
What is P-9A power supply and its automatic starting pressure?
Power Supply – Bus-13, Bkr 52-1305
PS-1311 starts pump at 98 psig fire main pressure
Where can P-9A be started?
Locally only at C-36. Indication and alarm for start in control room.
When does P-9B Start?
PS-1310 @ 83 psig lowering.
What are the details of starting/stopping P-9B from control room and locally?
What auto starts P-41?
PS-5350 @ 68 psig lowering
What are the details of starting/stopping P-41 from control room and locally?
Where are the fire pump control switches?
P-9A
P-9B
P-41
How does P-13, Jockey Pump start/stop?
Maintains header pressure to prevent water hammer.
Starts/Stop with P-9A breaker contacts
Will continue to run with P-9B/P-41 running.
Where is dry pipe sprinklers typically used?
Areas subjected to freezing temperatures.
Melting of fusible sprinkler head releases air pressure allowing water valves to open – water flows through melted sprinkler heads only
How does an ionization detector function?
Small amount of Americium provides a radiation field between charged plates
Smoke entering between charged plates causes a change in voltage to occur which actuates an alarm
How does a Photo-electric Detector work?
How does an Ultraviolet Detector work?