What is the purpose of the Pressurizer Pressure Control System?
Designed to maintain and control the Primary Coolant System (PCS) pressure 2010 psia to 2100 psia during power operation. through the use of a Pressurizer, where steam and water are maintained in thermal equilibrium.
Also provides overpressure protection for the PCS when the system temperature is below 430º F
How do PIC-0101A and PIC-0101B function?
Maintains pressure 2010 psia to 2100 psia during power operation
AUTO - normal mode of operation
MANUAL
What occurs with varying signal output from PIC-0101A/B?
0% to 33.3%
What are the controls and indications for PIC-0101A/B?
RED Light Lit - Failure, call I&C
AMBER Light Lit - Alarm, plant below 1500 psia or call I&C
CASCADE - no function
RED (left) Pointer - indicates system pressure
BLUE (right) Pointer - Operator controlled setpoint
AUTO - pushing places controller in Auto
MANUAL - pushing places controller in manual
BOTTOM SIGNAL METER - output of controller
What are the power supplies to PIC-0101A/B?
PIC-0101A - Y10.
PIC-0101B - Y20.
PIC fails to 0% output upon loss of power to the controller (heaters fully on).
What is the purpose of 1/PRC-0101, Control Selector?
1/PRC-0101
Select PIC-0101A or PIC-0101B for output to Spray/Heaters
Unselected Pressurizer pressure controller is MANUAL, with a 50% output signal.
What is the function of the pressurizer heaters?
Maintain thermal equilibrium at approximately 640º F (Tsat for 2060 psia)
To limit the pressure drop and restore pressure to controller set point during transients and normal operations.
Sized to heat up the PZR at zero power programmed level at a rate which maintains about 200 psia subcooling as the PCS is heated by decay heat and pump heat.
One half of the heater capacity (nominally 750 KW) provides sufficient capacity to establish and maintain natural circulation in hot standby conditions.
What are the Pressurizer Heater Groups and power supplies?
Backup heaters - four groups.
What is the ouput of the pressurizer heaters? What is T.S. requried?
12.5 KW. / heater
1500 KW for all heaters (Proportional and backup).
Normal power consumption is 145 amps for each LCC 15 and 16
PZR heater capacity of 117.5 amps on each Heater Transformer (LCC 15 and LCC 16) is required to satisfy Technical Specification LCO 3.4.9 b and c to have greater than or equal to 375 kW of Pressurizer heater capacity on bus 1D and bus 1E.
What are the backup heater controls and indications?
What is the Proportional heater control?
Proportional heaters
Two groups with 6 heaters/group.
Voltage Regulation based on signal from PIC-0101A/B
Proportional heater Handswitches (Group 1, 2):
Proportional heater indication lights:
What is the Pressure Control Strategy?
Backup Heaters On (in manual)
Pressurizer held steady at 2060 psia
Controller Output - 66%
Advantages
What is the Pressurizer Heater Level Trip?
Pressurizer Level Heater Trip
36% - Heater Control Selector switch trips heaters
Heater breaker from Bus 1E (LCC‑15), will reclose when Pressurizer level > 36%
Heater breaker from Bus 1D (LCC‑16), will NOT reclose when Pressurizer level > 36%
What is the design and motive force for CV-1057, CV-1059?
CV-1057, CV-1059
Parallel 3” air to open spray control valves.
Combine into a single four-inch line connected to a single spray head.
¾” flow adjustable manual bypass valve throttled to approximately 1 gpm flow.
What loops are the spray valves off of and what is spray flow under varying conditions?
CV-1057
CV‑1059
Spray Flows
What are the controls and indications for CV-1057/1059?
Spray Valve Handswitches (CV-1057/1059):
Spray Valve indications (CV-1057/1059):
What is Auxiliary Spray Control Valve (CV-2117)?
Auxiliary Spray Control Valve (CV-2117)
Air to Open (Open/Closed no throttling)
On 2-inch line from charging pumps
Used during startups/shutdowns or for pressure control during natural circulation, i.e., PCPs NOT available.
What are the requirements for logging spray cycles?
If Pressurizer sprays (main or auxiliary) are operated when differential temperature
between spray water and Pressurizer vapor phase is greater than 200F, then
perform the following:
What is LTOP?
Low Temperature Overpressure Protection Operations (LTOP)
What are the LTOP Control Units (PY-0105A and PY-0105B) and their power supplies?
PY-0105A and PY-0105B
Calculates a pressure setpoint based on cold leg temperature.
Will actuate the PORVs if the calculated pressure setpoint is exceeded.
Power Supplies
What are the inputs into LTOP?
PT-0104A/B, Pressurizer Narrow Range Pressure - Low Range
PT-0105A/B, Pressurizer Wide Range Pressure
TT‑0112CA, Cold Leg Temperature
TT-0122CB, Cold Leg Temperature
‘A’ Channel inputs into PY-0105A.
‘B’ Channel inputs into PY-0105B
What is the LTOP use of temperature input?
The LTOP computer in the shutdown-cooling mode does NOT use the temperature input to LTOP, but that failure of the temperature input will render the LTOP channel out of service.
The LTOP logic is designed to prevent any automatic actuation with a failed temperature input.